Plan Review Notes For Permit 02110587 |
Permit Number |
02110587 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-20 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | PRIVATE SWIMMING POOLS. (ADD TO NOTES) | | 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 3) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 4) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | LED WITH FLANGES OR UNION CONNECTIONS | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | 5) SECTION 104.2 - DRAWINGS SHALL BE OF | | SUFFICIENT CLARITY. COPIES OF COPIES ARE | | GETTING DIFFICULT TO READ FOR DETAILS | | AND NOTES. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|