Plan Review Notes For Permit 02110460 |
Permit Number |
02110460 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-09 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) GAS SYSTEM IS AN ENGINEERED, SIGNED | | AND SEALED SYSTEM. PLEASE SUBMIT A SIGN- | | EN AND SEALED GAS RISER DIAGRAM. THE GAS | | RISER DIAGRAM SUBMITTED DOES NOT MATCH | | THE ENGINEERED RISER. | | 2) ENGINEERED PLANS STATE THAT IT IS AN | | "LP" SYSTEM AND APPLICATION/PLANS NOT | | SUBMITTED STATE THAT THE SYSTEM IS USING | | NATURAL GAS. PLEASE CLAIRFY. | | 3) APPLICATION FOR "LP" WILL NEED AN LP | | LICENSE. | | 4) MANUFACTURE INFORMATION SUBMITTED IS | | NOT READABLE, AND DOES NOT SHOW ANY | | LISTING ON SUBMITTAL. | | 5) PLEASE HAVE ENGINEER OF RECORD ADD- | | RESS THESE DISCREPENCIES OF GAS TYPE AND | | RISER DIAGRAMS AND RESUBMIT. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|