Plan Review Notes
Plan Review Notes For Permit 02110460
Permit Number 02110460
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) GAS SYSTEM IS AN ENGINEERED, SIGNED
 AND SEALED SYSTEM. PLEASE SUBMIT A SIGN-
 EN AND SEALED GAS RISER DIAGRAM. THE GAS
 RISER DIAGRAM SUBMITTED DOES NOT MATCH
 THE ENGINEERED RISER.
 2) ENGINEERED PLANS STATE THAT IT IS AN
 "LP" SYSTEM AND APPLICATION/PLANS NOT
 SUBMITTED STATE THAT THE SYSTEM IS USING
 NATURAL GAS. PLEASE CLAIRFY.
 3) APPLICATION FOR "LP" WILL NEED AN LP
 LICENSE.
 4) MANUFACTURE INFORMATION SUBMITTED IS
 NOT READABLE, AND DOES NOT SHOW ANY
 LISTING ON SUBMITTAL.
 5) PLEASE HAVE ENGINEER OF RECORD ADD-
 RESS THESE DISCREPENCIES OF GAS TYPE AND
 RISER DIAGRAMS AND RESUBMIT.
  