Plan Review Notes
Plan Review Notes For Permit 02110371
Permit Number 02110371
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT.
 2-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE. TABLE REFERENCED ON DETAIL 11/S3
 IS FOR CONCRETE WALL ASSEMBLIES, NOT
 FOR WOOD CONSTRUCTION. SEE SECTION
 709.6 FBC FOR WOOD ASSEMBLIES AND NEED
 TO COMPLETE DETAIL PROVIDING SPECS FOR
 INTERIOR AND EXTERIOR EXPOSURE TO FIRE
 AS REQUIRED BY TABLE 600 FBC 2001.
 3-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 5-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.