Plan Review Notes For Permit 02110371 |
Permit Number |
02110371 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE SOIL TEST REPORT. | | 2-ARCHITECT TO REVISE DETAIL FOR ONE HR | | FIRE RATED WALL ASSEMBLY AT ZERO LOT | | LINE. TABLE REFERENCED ON DETAIL 11/S3 | | IS FOR CONCRETE WALL ASSEMBLIES, NOT | | FOR WOOD CONSTRUCTION. SEE SECTION | | 709.6 FBC FOR WOOD ASSEMBLIES AND NEED | | TO COMPLETE DETAIL PROVIDING SPECS FOR | | INTERIOR AND EXTERIOR EXPOSURE TO FIRE | | AS REQUIRED BY TABLE 600 FBC 2001. | | 3-ARCHITECT TO REVISE THE DIAPHRAGM | | SCHEDULE TO MATCH ENGINEERING ANALYSIS | | AND SPECIFICATIONS. | | 4-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 5-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. NEED ANCHOR SIZE AND WASHER. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|