Plan Review Notes
Plan Review Notes For Permit 02110368
Permit Number 02110368
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE WALL. TABLE REFERENCED ON DETAIL
 11/S3 IS FOR CONCRETE ASSEMBLIES, NOT
 FOR WOOD. SEE SECTION 709.6 FBC FOR
 WOOD ASSEMBLIES AND REVISE DETAIL AS
 REQUIRED. ALSO, COMPLETE DETAIL
 INCLUDING ASEMBLY REQUIRED AT EXTERIOR
 SIDE. NEED ONE HR FROM INTERIOR AND
 EXTERIOR EXPOSURE TO FIRE AS REQUIRED
 BY TABLE 600 FBC 2001.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.