Plan Review Notes For Permit 02110364 |
Permit Number |
02110364 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR | | FIRE RATED WALL ASSEMBLY AT ZERO LOT | | LINE WALL. TABLE REFERENCED ON DETAIL | | 11/S3 IS FOR CONCRETE WALL ASSEMBLIES, | | NOT FOR WOOD. SEE SECTION 709.6 FBC | | FOR WOOD ASSEMBLIES. AND COMPLETE | | DETAIL SHOWING ASSEMBLY CONSIDERING | | BOTH INTERIOR AND EXTERIOR EXPOSURE TO | | FIRE AS REQUIRED BY TABLE 600 FBC 2001 | | 2-ARCHITECT TO REVISE DIAPHRAGM SCHEDULE | | TO MATCH ENGINEERING ANALYSIS AND | | SPECIFICATIONS. | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. NEED ANCHOR SIZE AND WASHER. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|