Plan Review Notes
Plan Review Notes For Permit 02110364
Permit Number 02110364
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE WALL. TABLE REFERENCED ON DETAIL
 11/S3 IS FOR CONCRETE WALL ASSEMBLIES,
 NOT FOR WOOD. SEE SECTION 709.6 FBC
 FOR WOOD ASSEMBLIES. AND COMPLETE
 DETAIL SHOWING ASSEMBLY CONSIDERING
 BOTH INTERIOR AND EXTERIOR EXPOSURE TO
 FIRE AS REQUIRED BY TABLE 600 FBC 2001
 2-ARCHITECT TO REVISE DIAPHRAGM SCHEDULE
 TO MATCH ENGINEERING ANALYSIS AND
 SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.