Plan Review Notes For Permit 02110363
Permit Number 02110363
Review Stop R
Sequence Number 2
Notes
Date Text
2003-03-10 00:00:00REVISION CHECKLIST:
 1-ARCHITECT NEEDS TO REVIEW ENGINEERING
 CALCULATIONS AND SPECS AND REVISE THE
 DIAPHRAGM SCHEDULE AS REQUIRED.
 2-SHEET A-3: REVISE RIGHT ELEVATION TO
 MATCH BUILDING SECTION A/A-3. TOP OF
 BB WAS RAISED TO AVOID 1HR. FIRE RATED
 ASSEMBLY AT TRUSS HEEL @ ZERO LOT LINE
 WALL. SEE PLANS FOR COMMENTS.
 ALSO, REVISE BEAM HEIGHT SHOW ON OTHER
 ELEVATIONS AND ROOF FRAMING PLAN.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT AS
 REQUESTED ON PROVISO DATED 12-15-02.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED COMPLETE SIZE OF ANCHOR &
 WASHER. SEC. 104.2.1.2 CITY AMENDMENTS
 5-SHEET S-2: DETAIL 8/S-2 WAS KEYED
 INCORRECTLY. SEE PLAN AND REVISE AS
 REQUIRED.