Plan Review Notes
Plan Review Notes For Permit 02110363
Permit Number 02110363
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE. TABLE REFERENCED ON DETAIL 11/S3
 IS FOR CONCRETE WALL ASSEMBLY, NOT FOR
 WOOD CONSTRUCTION. SEE SECTION 709.6
 FBC FOR WOOD ASSEMBLIES AND PROVIDE
 COMPLETE DETAIL SHOWING ASSEMBLY FOR
 BOTH SIDES INTERIOR AND EXTERIOR
 EXPOSED TO FIRE AS REQUIRED BY TABLE
 600 FBC 2001.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.