Plan Review Notes For Permit 02110363 |
Permit Number |
02110363 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR | | FIRE RATED WALL ASSEMBLY AT ZERO LOT | | LINE. TABLE REFERENCED ON DETAIL 11/S3 | | IS FOR CONCRETE WALL ASSEMBLY, NOT FOR | | WOOD CONSTRUCTION. SEE SECTION 709.6 | | FBC FOR WOOD ASSEMBLIES AND PROVIDE | | COMPLETE DETAIL SHOWING ASSEMBLY FOR | | BOTH SIDES INTERIOR AND EXTERIOR | | EXPOSED TO FIRE AS REQUIRED BY TABLE | | 600 FBC 2001. | | 2-ARCHITECT TO REVISE THE DIAPHRAGM | | SCHEDULE TO MATCH ENGINEERING ANALYSIS | | AND SPECIFICATIONS. | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. NEED ANCHOR SIZE AND WASHER. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|