2002-12-11 00:00:00DENIED:
  
 1.PROVIDE ENERGY & MANUAL J CALCS.
  
 2.PLAN SHEET A-5 MECHANICAL NOTE #10,
 AHU INSTALLED ON BENCH OR STAND AS
 SHOWN ON PLAN.PLANS INDICATE
 AHU HANGING IN ATTIC.PROVIDE
 DETAIL FOR HANGING.PLEASE NOTE
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED AS PER 2001
 FBC(M) 307.2.3.
  
 3.ACCESS OPENING TO AHU SHALL BE NO
 LESS THAN 20" X 30". 2001 FBC(M)
 306.3
  