Plan Review Notes For Permit 02110299 |
Permit Number |
02110299 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-11 00:00:00 | DENIED: | | | | 1.PROVIDE ENERGY & MANUAL J CALCS. | | | | 2.PLAN SHEET A-5 MECHANICAL NOTE #10, | | AHU INSTALLED ON BENCH OR STAND AS | | SHOWN ON PLAN.PLANS INDICATE | | AHU HANGING IN ATTIC.PROVIDE | | DETAIL FOR HANGING.PLEASE NOTE | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED AS PER 2001 | | FBC(M) 307.2.3. | | | | 3.ACCESS OPENING TO AHU SHALL BE NO | | LESS THAN 20" X 30". 2001 FBC(M) | | 306.3 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|