Plan Review Notes For Permit 02110299 |
Permit Number |
02110299 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-14 00:00:00 | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE AND COMPLY WITH THE | | FOLLOWING BEFORE CALLING ROUGH | | INSPECTION. | | | | 1} A DISCONNECT IS REQUIRED PER | | 230-70(A)CWPB,IF THERE IS MORE THAN | | 8'OF SERVICE CONDUCTORS ARE INSIDE THE | | BUILDING PER 230-6. | | | | 2} THE RELOCATED SERVICE MUST COMPLY | | WITH 250-50(A)(B)& (C),CWP,ROD,AND | | FOOTER STEEL. | | | | 3} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG.,ON THE PANEL | | SCHEDULE. | | | | 4} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | 5} ALL RECEPTALES SERVING COUNTERTOPS | | MUST BE GFCI PROTECTED PER 210-8(A)(7) | | CWBP. | | | | 6} AHU IN ATTIC MUST COMPLY WITH 210-63 | | & 210-70(A)(3). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|