Plan Review Notes
Plan Review Notes For Permit 02110299
Permit Number 02110299
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE AND COMPLY WITH THE
 FOLLOWING BEFORE CALLING ROUGH
 INSPECTION.
  
 1} A DISCONNECT IS REQUIRED PER
 230-70(A)CWPB,IF THERE IS MORE THAN
 8'OF SERVICE CONDUCTORS ARE INSIDE THE
 BUILDING PER 230-6.
  
 2} THE RELOCATED SERVICE MUST COMPLY
 WITH 250-50(A)(B)& (C),CWP,ROD,AND
 FOOTER STEEL.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.,ON THE PANEL
 SCHEDULE.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} ALL RECEPTALES SERVING COUNTERTOPS
 MUST BE GFCI PROTECTED PER 210-8(A)(7)
 CWBP.
  
 6} AHU IN ATTIC MUST COMPLY WITH 210-63
 & 210-70(A)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392