Plan Review Notes For Permit 02110299 |
Permit Number |
02110299 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-11 00:00:00 | SHEET A4 CITES DESIGN TO THE UBC.THE | | 2001 FLORIDA BUILDING CODE IS IN | | EFFECT. PLEASE REVISE AND ENSURE | | COMPLIANCE WITH SAME. | | | | THE PLANS DO NOT SHOW THE DESIGN | | PRESSURES FOR THE COMPONENTS AND | | CLADDING, WALLS AND ROOF. | | SEE FBC 1606.1.7. | | | | SHOW THE ATTIC ACCESS IN ACCORDANCE WITH | | FBC 2309.6. | | | | SHOW THE MINIMUM INFORMATION FOR THE | | REINFORCED MASONRY.SEE FBC 2103.1. | | | | THE BEAM SCHEDULE ON SHEET A4 CALLS OUT | | 4 #5 T&B.THE TYPICAL WALL SECTION (1) | | ON SHEET A3 INDICATES A DOUBLE BOND BEAM | | WITH #7 BARS.PLEASE CLARIFY DESIGN | | INTENT. | | | | THE MIAMI-DADE NOTICE OF ACCEPTANCE'S | | 02-0129.01, 01-0323.02 AND 01-0516.10 | | HAVE ILLEGIBLE DRAWINGS.PLEASE PROVIDE | | CLEAR COPIES. | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY, THE PERMIT PLANS | | STAMPED BY THAT OFFICE, AND A COPY OF | | THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL 233-5025 FOR MORE | | INFORMATION. |
|