2003-03-07 00:00:00SUBMITTAL CHECKLIST:
 1-ARCHITECT NEEDS TO REVIEW ENGINEERING
 CALCULATIONS AND REVISE THE DIAPHRAGM
 SCHEDULE AS REQUIRED.
 2-SHEET A-3: REVISE RIGHT ELEVATION TO
 MATCH BUILDING SECTION A/A3.TOP OF
 BB WAS RAISED TO AVOID ONE HR ASSEMBLY
 AT TRUSS HEEL AREA AT ZERO LOT LINE
 WALL.
 3-SHEET S-2: DETAIL 8/S2 WAS INCORRECTLY
 KEYED. SEE 2ND FLOOR FRAMING PLAN AND
 REVISE AS REQUIRED.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT AS
 REQUESTED ON PROVISO DATED 12-10-02.
 5-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED COMPLETE ANCHOR SIZE AND
 WASHER. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.