Plan Review Notes
Plan Review Notes For Permit 02110226
Permit Number 02110226
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-10 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 WALL ASSEMBLY AT ZERO LOT LINE.
 TABLE REFERENCED ON DETAIL 11/S3 IS
 FOR CONCRETE WALL ASSEMBLIES, NO WOOD.
 SEE SECTION 709.6 FOR WOOD ASSEMBLIES
 AND PROVIDE COMPLETE DETAIL FOR ONE HR
 ASSEMBLY WITH PROTECTION FROM EXTERIOR
 AND INTERIOR AS REQUIRED BY TABLE 600
 FBC 2001.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED ANCHOR SIZE AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.