Plan Review Notes
Plan Review Notes For Permit 02110224
Permit Number 02110224
Review Stop R
Sequence Number 2
Notes
Date Text
2003-03-10 00:00:00REVISION CHECKLIST:
 1-ARCHITECT NEED TO REVIEW ENGINEERING
 CALCULATIONS AND SPECS AND REVISE THE
 DIAPHRAGM SCHEDULE AS REQUIRED.
 2-ARCHITECT TO REVISE RIGHT ELEVATION
 TO MATCH BUILDING SECTION A-A3. TOP OF
 BB WAS RAISED TO AVOID 1 HR FIRE RATED
 ASSEMBLY AT TRUSS HEEL AS REQUIRED BY
 TABLE 600 FBC 2001. THEREFORE, NOTE
 #4 DOESN'T APPLY ANYMORE.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT AS
 REQUESTED ON PROVISO DATED 12-12-02.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED COMPLETE ANCHOR SIZE AND
 WASHER. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.