Plan Review Notes For Permit 02110224
Permit Number 02110224
Review Stop R
Sequence Number 1
Notes
Date Text
2002-12-12 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 WALL ASSEMBLY AT ZERO LOT LINE.
 TABLE REFERENCED ON DETAIL 11/S3 IS
 FOR CONCRETE WALL ASSEMBLIES, NO WOOD.
 REVISE, SEE SEC. 709.6 FBC AND PROVIDE
 ASSEMBLY FOR ONE HR PROTECTION AT
 EXTERIOR AND INTERIOR AS REQUIRED BY
 TABLE 600 FBC 2001.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING ANALYSIS
 AND SPECIFICATIONS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41 OF S1. NEED ANCHOR BOLT SIZE AND
 WASHER. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.