1 |
|
Notes |
Date |
Text |
2002-11-14 00:00:00 | ************* UNSAT *************** | | | | 1)NOTE: PLEASE NOTE, PLANS DO NOT | | CORRELATE WITH MASTER.02041264 | | | | 2)NOTE: PLEASE SEE MISSING ARC FAULT | | PER 210-12 | | | | 3)NOTE: PLEASE SEE MISSING BATH(S) | | CIRCUITS PER210-11-C3 | | | | 4)NOTE: PLEASE SEE DRYER SHOWN AT 1-POLE | | 20A BRKR. | | | | PLEASE SEE OTHER CHANGES ON PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|