Plan Review Notes
Plan Review Notes For Permit 02110202
Permit Number 02110202
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT
 CORRELATE WITH MASTER.02041264
  
 2)NOTE: PLEASE SEE MISSING ARC FAULT
 PER 210-12
  
 3)NOTE: PLEASE SEE MISSING BATH(S)
 CIRCUITS PER210-11-C3
  
 4)NOTE: PLEASE SEE DRYER SHOWN AT 1-POLE
 20A BRKR.
  
 PLEASE SEE OTHER CHANGES ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  