2002-11-19 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM AND
 PANEL SCHEDULE DO NOT CORRELATE FOR
 "H1B". PLEASE NOTE, ORIG SHEET SHOWS
 RISER AS "H2B. PLEASE NOTE RISER IS
 NOW CHANGED BUT PANEL SCHEDULE FOR TRANS
 -FORMER SHOWS ,, PANEL "LA" FED THRU
 TRANSFORMER "TB1". PLEASE SEE RISER
 DIAGRAM, PANEL LA IS SHOWN AS PART OF
 EXSITING SERVICE? X-FORMER IS ALSO
 SHOWN AS T1B? PLEASE NOTE RISER DIAGRAM
 SHOWS NEW TRANSFORMER " T1C" AND L1B,
 L1C, ETC.
  
 2)NOTE: PLEASE NOTE, NOT #2 FROM FIRST
 REVIEW NEEDS TO BE ADDRESSED. PLEASE
 CLARIFY REQ`D RECEPT FOR A/C UNITS
 PER 210-63.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  