Plan Review Notes For Permit 02110163 |
Permit Number |
02110163 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-11-19 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM AND | | PANEL SCHEDULE DO NOT CORRELATE FOR | | "H1B". PLEASE NOTE, ORIG SHEET SHOWS | | RISER AS "H2B. PLEASE NOTE RISER IS | | NOW CHANGED BUT PANEL SCHEDULE FOR TRANS | | -FORMER SHOWS ,, PANEL "LA" FED THRU | | TRANSFORMER "TB1". PLEASE SEE RISER | | DIAGRAM, PANEL LA IS SHOWN AS PART OF | | EXSITING SERVICE? X-FORMER IS ALSO | | SHOWN AS T1B? PLEASE NOTE RISER DIAGRAM | | SHOWS NEW TRANSFORMER " T1C" AND L1B, | | L1C, ETC. | | | | 2)NOTE: PLEASE NOTE, NOT #2 FROM FIRST | | REVIEW NEEDS TO BE ADDRESSED. PLEASE | | CLARIFY REQ`D RECEPT FOR A/C UNITS | | PER 210-63. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|