Plan Review Notes
Plan Review Notes For Permit 02110163
Permit Number 02110163
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-13 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, RISER DIAGRAM
 AND SUBMITTED PANEL SCHEDULES DO NOT
 CORRELATE. MISSING PANEL "H2B, MISSING
 "L2C", LOAD CALCULATIONS,CIRCUIT #`S
 WIRE SIZES ETC.
 PLEASE NOTE, THERE ARE PANEL SCHEDULES
 SUBMITTED NOT ON RISER? "H1B", PLEASE
 CLARIFY.215-5
 PLEASE NOTE AT THIS TIME A COMPLETE
 REVIEW OF WIRE/OCP/LOADS CAN NOT BE DONE
 UNTIL RISER/PLANS/SCHEDULES CORRELATE.
  
 2)NOTE: PLEASE NOTE/CLARIFY RECEPT REQ`D
 FOR A/C EQUIPMENT ON ROOFTOP. NEW/ EXIST
 ? 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372