2002-11-13 00:00:00THE DOOR EXITING "OPEN OFFICE 124" ON
 THE SOUTH SIDE OF THE TOILET ROOMS
 SHOWN AS "EXT" IS REQUIRED TO SWING IN
 THE DIRECTION OF EXIT TRAVEL.SEE FBC
 1012.1.2 AND FBC 1012.1.4.
  
 THE DOOR AND SIDE LIGHT SHOWN AS 109
 NEAR THE NORTH STAIR IS REQUIRED TO BE
 FIRE RATED.SEE FBC 1010.1.
  
 SHOW THE DESIGN WIND PRESSURE FOR THE
 NEW STORE FRONT DOOR.SEE FBC 1606.1.7.
  
 IF THE TEST REPORTS AND/OR NOTICE OF
 ACCEPTANCE REPORTS ARE NOT INCLUDED
 WITH THIS PERMIT APPLICATION, A
 SEPARATE PERMIT, PLANS AND FEES WILL BE
 REQUIRED.