2002-11-13 00:00:00 | THE DOOR EXITING "OPEN OFFICE 124" ON | | THE SOUTH SIDE OF THE TOILET ROOMS | | SHOWN AS "EXT" IS REQUIRED TO SWING IN | | THE DIRECTION OF EXIT TRAVEL.SEE FBC | | 1012.1.2 AND FBC 1012.1.4. | | | | THE DOOR AND SIDE LIGHT SHOWN AS 109 | | NEAR THE NORTH STAIR IS REQUIRED TO BE | | FIRE RATED.SEE FBC 1010.1. | | | | SHOW THE DESIGN WIND PRESSURE FOR THE | | NEW STORE FRONT DOOR.SEE FBC 1606.1.7. | | | | IF THE TEST REPORTS AND/OR NOTICE OF | | ACCEPTANCE REPORTS ARE NOT INCLUDED | | WITH THIS PERMIT APPLICATION, A | | SEPARATE PERMIT, PLANS AND FEES WILL BE | | REQUIRED. |
|