Plan Review Notes
Plan Review Notes For Permit 02110132
Permit Number 02110132
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE DO NOT CORRELATE
 WITH MASTER PLANS.02041269
  
 2)NOTE: MISSING ARC FAULT PROTECTION
 FOR BEDROOM CRICUITS PER 210-12
  
 3)NOTE: MISSING REQ`D BATH CIRCUIT(S)
 PER 210-11-C-3
  
 4)NOTE: PLEASE SEE DRYER SHOWN AT 1-POLE
 20A BRKR.
  
 PLEASE SEE PLANS, OTHER CHANGES WERE
 MADE ALSO.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EDXT 8372