2002-12-30 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| ***NOTE***: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| STATES THAT A LOCAL GOVERNMENT SHALL |
| IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 12/23/02: |
| |
| 2) FBC* 104.2.2SOME OF THE |
| ARCHITECTURAL SHEETS ARE STILL NOT |
| PROPERLY SEALED, FLORIDA STATUTES |
| 61G1-16.001 THRU 16.003.SEE NOTE ABOVE |
| |
| 3) SHEET A-05.THE AMENDMENT TO THE |
| INTERMEDIATE TRUSS ANCHOR FOR GIRDER |
| TRUSS SG2 IS NOTED, BUT THE ANCHORS AT |
| THE ENDS OF THIS TRUSS HAVE STILL NOT |
| BEEN AMENDED.WHEN THE TRUSS WAS MOVED |
| TOWARD THE REAR OF THE BUILDING, THE |
| RELEVANT TRUSS ANCHOR ANNOTATION WAS NOT |
| AMENDED TO SUIT.AS A RESULT OF THIS, |
| THE PLANS CURRENTLY SHOW A TRUSS ANCHOR |
| MARK A (UPLIFT CAPACITY 860 LBS) AT EACH |
| END OF THIS TRUSS.IS THIS INTENTIONAL/ |
| SUFFICIENT?.THE PREVIOUS TRUSS END |
| ANCHOR ANNOTATION FOR THIS TRUSS IS |
| STILL SHOWN ON THE PLAN BUT NOT POINTING |
| TO ANY TRUSS UNDER THE REVISED LAYOUT. |
| ALSO, THE 'REQUIRED UPLIFT' AND TRUSS |
| ANCHOR REFERENCES ON THE LEFT EDGE OF |
| SHEET A-05 HAVE NOT PRINTED (TRUNCATED |
| BY LEFT MARGIN).FINALLY, DUE TO |
| RELOCATION OF GIRDER TRUSS SG2, THE |
| AMENDED INTERMEDIATE TRUSS ANCHOR |
| 'MARK J' IS NOT ALIGNED WITH A CMU |
| COLUMN AND NO TIE BEAM IS SPECIFIED, ON |
| SHEET A-05, AT THE HEAD OF THE COVERED |
| PATIO SIDE WALL.SHOW THE MEANS FOR |
| TRANSFERRING THE LOADS FROM THE TRUSS |
| ANCHOR TO THE CMU WALL. |