Plan Review Notes
Plan Review Notes For Permit 02110129
Permit Number 02110129
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PLANS DO NOT
 CORRELATE WITH MASTER PLANS.
 UNDER #02041267
  
 2)NOTE: PLEASE SEE THE REQ`D MISSING
 BATH(S) CIRCUITS PER 210-52D, 210-11-C3
  
 3)NOTE: PLEASE SEE THE REQ`D ARC FAULT
 PROTECTED CIRCUITS HAVE BEEN REMOVED?
 210-12
  
 4)NOTE: PLEASE NOTE DRYER CIRCUIT SHOWN
 AS 1-POLE 20A?
  
 PLEASE SEE ORIG PLANS ANDS SEE OTHER
 CHANGES THAT HAVE BEEN MADE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372