Plan Review Notes For Permit 02110128 |
Permit Number |
02110128 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-14 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE, PLANS DO NOT | | CORRELATE WITH MASTER PLANS #02041257 | | | | 2)NOTE: PLEASE NOTE THE REQ`D DEDICATED | | BATH(S) CIRCUITS HAVE BEEN REMOVED? | | 210-52D,210-11-C3 | | | | 3)NOTE: PLEASE NOTE THE REQ`D ARC FAULT | | PROTECTED CIRCUITS HAVE ALSO BEEN | | REMOVED? 210-12 | | | | 4)NOTE: PLEASE NOTE DRYER SHOWN AS | | 1-POLE 20A? | | | | 5)NOTE: PLEASE SEE OTHER ITEMS ON PLANS | | THAT HAVE CHANGED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|