2002-11-14 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT
 CORRELATE WITH MASTER PLANS #02041257
  
 2)NOTE: PLEASE NOTE THE REQ`D DEDICATED
 BATH(S) CIRCUITS HAVE BEEN REMOVED?
 210-52D,210-11-C3
  
 3)NOTE: PLEASE NOTE THE REQ`D ARC FAULT
 PROTECTED CIRCUITS HAVE ALSO BEEN
 REMOVED? 210-12
  
 4)NOTE: PLEASE NOTE DRYER SHOWN AS
 1-POLE 20A?
  
 5)NOTE: PLEASE SEE OTHER ITEMS ON PLANS
 THAT HAVE CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372