Plan Review Notes
Plan Review Notes For Permit 02110127
Permit Number 02110127
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT
 CORRELATE TO MASTER PLANS UNDER 02041264
  
 2)NOTE: PLEASE NOTE DEDICATED BATH(S)
 CIRCUITS HAVE BEEN REMOVED. 210-52D
 210-11-C3
  
 3)NOTE: PLEAS ALSO NOTE THE REQ`D
 DEDICATED ARC FAULT CIRCUITS PER 210-12
 HAVE BEEN REMOVED?
  
 4)NOTE: PLEASE NOTE DRYER SHOWN AS
 1-POLE 20A?
  
 PLEASE NOTE OTHER ITEMS ON PLANS THAT
 HAVE BEEN CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW