Plan Review Notes
Plan Review Notes For Permit 02110125
Permit Number 02110125
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00************** UNSAT ************
  
 1)NOTE : PLEASE NOTE PLANS DO NOT
 CORRELATE TO THE MASTER PLAN SUBMITTED
 UNDER 02041269.
 PLANS MUST BE THE SAME.
  
 2)NOTE: PLEASE SEE THE REQ`D DEDICATED
 BATH(S) CIRCUITS HAVE BEEN REMOVED?
 210-52D,210-11-C3
  
 3)NOTE: PLEASE SEE THE REQ`D ARC FAULT
 CIRCUITS HAVE ALSO BEEN REMOVED ??
 210-12
  
 4)NOTE: PLEASE SEE ORIG PLANS AND SEE
 OTHER ITMES THAT HAVE BEEN CHANGED/
 REMOVED ETC.
  
 5)NOTE: PLEASE NOTE DRYER SHOWN AS A
 1-POLE 20A ?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372