Plan Review Notes For Permit 02110123 |
Permit Number |
02110123 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-12-12 00:00:00 | *********** NOTES REDLINED ******** | | | | PLEASE SEE PLANS FOR THE FOLLOWING. | | | | 1)NOTE: PLEASE NOTE DRYER STILL SHOWN | | AS 1-POLE 20A OCP FOR 5KW 240V CIRCUIT? | | PLEASE REVISE. | | | | 2)NOTE: SD ON SECOND FLR HALL NEEDS TO | | MOVED FROM LOCATION SHOWN OR ADD ANOTHER | | OUTSIDE BEDROOMS 2&3. | | | | | | PLEASE SUBMIT THE ABOVE REVISED AND | | SHOW ALL "OPTIONS" INSTALLED BEFORE | | ROUGH. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|