Plan Review Notes
Plan Review Notes For Permit 02110044
Permit Number 02110044
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO THE PLAN,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
 MUST HAVE A BATTERY BACK UP PER 905.2.5
 FBC.
  
 5} THE ISLAND IN THE KITCHEN MUST COMPLY
 WITH 210-52(C)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392