2002-12-03 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION,MAKE ANY NECESSARY CHANGES |
| TO THE PLAN,AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2} PLEASE LIST THE REQ'D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| |
| 3} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| CIRCUIT PROTECTION. PER 210-12 |
| |
| 4} SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| IN THE VICINITY OF BEDROOMS AND CLOSE |
| PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| MUST HAVE A BATTERY BACK UP PER 905.2.5 |
| FBC. |
| |
| 5} THE ISLAND IN THE KITCHEN MUST COMPLY |
| WITH 210-52(C)(2). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |