2002-12-05 00:00:00BUILDING DENIED
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A SIGNED AND SEALED SOIL TEST
 REPORT FROM A SOIL ENGINEER INDICATING
 THE SOIL BEARING CAPACITY.
  
 2) THE F4 FOOTINGS FOR THE COLUMNS AT
 THE COVERED PORCH ARE NOT GIVEN IN THE
 FOOTING SCHEDULE ON S1.
  
 3) SPECIFY THE WASHER SIZE FOR THE 1/2"
 J-BOLT SHOWN IN SECTION 3 ON S1.
  
 4) THE NAIL SPACING INDICATED FOR THE
 ROOF SHEATHING ON THE DETAILS ON S2 AND
 ON GN1 ARE NOT CORRECT. PLEASE CORRECT.
 SEE CITY OF WPB AMENDMENTS TO FBC TABLE
 23O6.1.
  
 5) CLARIFY THE SIZE OF THE DOOR TO THE
 CABANA BATH ON A1. THERE APPEARS TO BE A
 TYPO (210868 IS GIVEN).
  
 6) THE BUILT-UP WOOD POST COLUMN IS
 SPECIFIED AS (2) 2X4 ON S1 AND ON S3 IT
 IS GIVEN AS (3) 2X4. PLEASE CLARIFY.
  
 7) SUBMIT SIGNED AND SEALED ENGINEERED
 DRAWINGS FOR THE BUCKET CONNECTION SHOWN
 IN DETAIL D ON S2.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE OVAL AND ARCHED TOP
 FIXED GLASS WINDOWS.
  
 9) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  