2002-12-05 00:00:00 | BUILDING DENIED |
| |
| 1) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE A SIGNED AND SEALED SOIL TEST |
| REPORT FROM A SOIL ENGINEER INDICATING |
| THE SOIL BEARING CAPACITY. |
| |
| 2) THE F4 FOOTINGS FOR THE COLUMNS AT |
| THE COVERED PORCH ARE NOT GIVEN IN THE |
| FOOTING SCHEDULE ON S1. |
| |
| 3) SPECIFY THE WASHER SIZE FOR THE 1/2" |
| J-BOLT SHOWN IN SECTION 3 ON S1. |
| |
| 4) THE NAIL SPACING INDICATED FOR THE |
| ROOF SHEATHING ON THE DETAILS ON S2 AND |
| ON GN1 ARE NOT CORRECT. PLEASE CORRECT. |
| SEE CITY OF WPB AMENDMENTS TO FBC TABLE |
| 23O6.1. |
| |
| 5) CLARIFY THE SIZE OF THE DOOR TO THE |
| CABANA BATH ON A1. THERE APPEARS TO BE A |
| TYPO (210868 IS GIVEN). |
| |
| 6) THE BUILT-UP WOOD POST COLUMN IS |
| SPECIFIED AS (2) 2X4 ON S1 AND ON S3 IT |
| IS GIVEN AS (3) 2X4. PLEASE CLARIFY. |
| |
| 7) SUBMIT SIGNED AND SEALED ENGINEERED |
| DRAWINGS FOR THE BUCKET CONNECTION SHOWN |
| IN DETAIL D ON S2. |
| |
| 8)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR THE OVAL AND ARCHED TOP |
| FIXED GLASS WINDOWS. |
| |
| 9) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |