Plan Review Notes For Permit 02102229 |
Permit Number |
02102229 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-27 00:00:00 | ********** NOTES ******** | | PLANS REDLINED, OCP FOR AHU SHOWN AT 2P | | -25A FOR 10KW LOAD. NEEDS TO BE SIZED | | AT 125% MIN PER 424-3 |
|