Plan Review Notes
Plan Review Notes For Permit 02102229
Permit Number 02102229
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-27 00:00:00********** NOTES ********
 PLANS REDLINED, OCP FOR AHU SHOWN AT 2P
 -25A FOR 10KW LOAD. NEEDS TO BE SIZED
 AT 125% MIN PER 424-3