Plan Review Notes
Plan Review Notes For Permit 02102192
Permit Number 02102192
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-01 00:00:001) SECURITY DEVICES INSTALLED ON DOORS
 USED FOR EXITING MUST COMPLY WITH
 DELAYED EGRESS OR SPECIAL LOCKING
 ARRANGEMENTS FROM THE 2000 LSC, CHAPTER
 7.
  
 2) PLANS DO NOT INDICATE IF THE DOOR
 IS AN EXIT DOOR.
  
 3) IT IS NOT SURE IF DOOR IS FAIL SAFE
 OR FAIL SECURE. EXITING IS UNCLEAR.
  
 ON 11.1.02 CALLED JOHN L OF KNIGHT
 ELECTRIC. HE ADVISED HE WAS UNSURE OF
 SOME OF THE ANSWERS AND WOULD GET BACK
 TO US.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910