Plan Review Notes For Permit 02102183 |
Permit Number |
02102183 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A1.3 SECTION 11-4.22.4 IF TOILET | | STALLS ARE PROVIDED, THAN AT LEAST ONE | | SHALL BE A STANDARD TOILET STALL COMPLY- | | ING WITH 11-4.17. EACH TOILET ROOM SHALL | | COMPLY. | | 2) SHT A10.3 TYPICAL WATERPROOF MENBRANE | | DETAIL. AN ENGINEERED - SIGNED, SEALED, | | AND DATED SUBMITTAL OF WATERPROOFING DE- | | TAIL IS REQUIRED. | | 3) SHTS. P.1 & P.2, ALL INDIRECT WASTE | | SHALL DRAIN INTO A FLOOR SINK. SEC 802.3 | | FLOOR DRAINS ARE NOT AN APPROVED IN- | | DIRECT WASTE RECEPTOR. FLOOR SINKS SHALL | | BE LOCATED AS NOT TO PRESENT A TRIPPING | | HAZARD. | | 4) SHT P.3 RISER NOTE #6, ALL WATER | | FILTERS SHALL BE "NSF" APPROVED. PLEASE | | SUBMIT MANUF. INFO. | | 5) SHT P.5 FLOOR DRAIN SPECIFICATIONS, | | FD-3, FLOOR DRAINS NOT APPROVED FOR IN- | | DIRECT WASTE. ALL INDIRECT WASTE SHALL | | BE DRAINED TO A FLOOR SINK. (SEE REVIEW | | COMMENT #3). | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|