Plan Review Notes For Permit 02102183 |
Permit Number |
02102183 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-14 00:00:00 | DENIED: | | | | CLARIFY ACCESS FOR MAINTENANCE, SERVICE | | OR REPLACEMENT OF THE AHU'S AND ITS | | COMPONENTS.2001FBC(M) 306.1 | | | | INDICATE ELEVATION OF AHU'S. | | | | PROVIDE MANUFACTURER SUBMITTAL DATA ON | | THE STANDS FOR THE CONDENSER UNITS. | | SHOW COMPLIANCE WITH 2001 FBC TABLE | | 1511.7 - MINIMUM HEIGHT REQUIREMENT FROM | | ROOF SURFACE.SHOW ACCESS TO CONDENSER | | UNITS LOCATED ON THE ROOF. | | | | ADDITIONAL PERMIT REQUIRED FOR WALK IN | | COOLERS OR FREEZERS. PROVIDE SUBMITTAL | | DATA FROM MANUFACTURER. SHOULD CONDENSER | | UNIT BE REMOTE, SHOW LOCATION OF C.U. | | | | INDENTIFY CONDENSATE TERMINATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|