2002-11-14 00:00:00DENIED:
  
 CLARIFY ACCESS FOR MAINTENANCE, SERVICE
 OR REPLACEMENT OF THE AHU'S AND ITS
 COMPONENTS.2001FBC(M) 306.1
  
 INDICATE ELEVATION OF AHU'S.
  
 PROVIDE MANUFACTURER SUBMITTAL DATA ON
 THE STANDS FOR THE CONDENSER UNITS.
 SHOW COMPLIANCE WITH 2001 FBC TABLE
 1511.7 - MINIMUM HEIGHT REQUIREMENT FROM
 ROOF SURFACE.SHOW ACCESS TO CONDENSER
 UNITS LOCATED ON THE ROOF.
  
 ADDITIONAL PERMIT REQUIRED FOR WALK IN
 COOLERS OR FREEZERS. PROVIDE SUBMITTAL
 DATA FROM MANUFACTURER. SHOULD CONDENSER
 UNIT BE REMOTE, SHOW LOCATION OF C.U.
  
 INDENTIFY CONDENSATE TERMINATION.
  