2002-11-14 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE PLANS MUST BE SIGNED
 DTAED AND SEALED BY THE ENGINEER OF
 RECORD. REQ`D PER FS/FAC 471.025,
 471.003 H 1/ FBC 104.4.1.3
 FOR 277/480V
  
 2)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3,230-42
 ETC.
  
 3)NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B.
  
 4)NOTE: PLEASE CLARIFY HOW 700-12 IS MET
  
 5)NOTE: PLEASE SHOW ALL CIRCUIT ON PLANS
 AND CORRELATE WITH PANEL SCHEDULE.
  
 6)NOTE: PLEASE CLARIFY LOCATIONS OF MAIN
 -S. GROUPING OF MAINS PER 230-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  