Plan Review Notes For Permit 02102001 |
Permit Number |
02102001 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-19 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE SOIL TEST REPORT. | | 2-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 3-REVISE TRUSS CONNECTOR SCHEDULE ON | | SHEETS S-2 AND S-3. SEE USP CATALOGUE | | OR PROVIDE ENGINEERING CACULATIONS FOR | | VALUES DIFFERENT THAN THOSE PUBLISHED | | BY USP. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC 2001. | | 4-PROVIDE STRUCTURAL BUCK DETAIL FOR | | GARAGE DOOR WITH COMPLETE SIZE FOR | | ANCHOR BOLTS AND WASHERS. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|