Plan Review Notes For Permit 02101998 |
Permit Number |
02101998 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-04 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR | | FIRE RATED WALL ASSEMBLY AT ZERO LOT | | LINE WALL. TABLE REFERENCED ON DETAIL | | 11/S3 IS FOR CONCRETE WALL ASSEMBLIES, | | NOT WOOD. SEE SECTION 709.6 FBC 2001 | | FOR WOOD ASSEMBLIES AND NEED COMPLETE | | ASSEMBLY TAKING INTO CONSIDERATION | | INTERIOR AND EXTERIOR EXPOSURE TO FIRE | | AS REQUIRED BY TABLE 600 FBC 2001. | | 2-ARCHITECT TO REVISE THE DIAPHRAGM | | SCHEDULE TO MATCH ENGINEERING ANALYSIS | | AND SPECIFICATIONS. | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. NEED ANCHOR SIZE AND WASHER. | | COLUMN SCHEDULE DOESN'T HAVE ANY | | INFORMATION EITHER.SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. |
|