Plan Review Notes For Permit 02101997 |
Permit Number |
02101997 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-11 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO SPECIFY ONE HOUR FIRE | | RATED GLASS BLOCK ASSEMBLY AT ZERO LOT | | LINE WALL AS REQUIRED BY TABLE 600 | | FBC 2001. | | **GLASS BLOCK TO BE SAFETY GLASS IF FACE | | THICKNESS IS LESS THAN 0.25". SECTION | | 2405.2.2 FBC 2001. | | 2-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 4-REVISE DETAIL/SECTION 3 ON SHEET S-2 | | TO MATCH ENGINEERING CALCULATIONS AND | | THE DIAPHRAGM SCHEDULE. SEE FASTENERS | | SPECIFIED. | | 5-PROVIDE GENERAL SPECS FOR FIREBLOCKING | | AT ALL CONCEALED SPACES AS REQUIRED BY | | SEC. 2305.1.4 FBC 2001. | | 6-PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOOR WITH SIDELITE SINGLE ASSEMBLY AS | | SHOWN ON PLANS. (THIS PRODUCT APPROVAL | | WAS NOT SUBMITTED FOR MASTER PRODUCT | | APPROVAL PACKAGE). |
|