Plan Review Notes
Plan Review Notes For Permit 02101988
Permit Number 02101988
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO REVISE DETAIL FOR ONE HR
 FIRE RATED WALL ASSEMBLY AT ZERO LOT
 LINE. TABLE REFERENCED ON DETAIL 11/S3
 IS FOR CONCRETE WALL ASSEMBLIES, NOT
 FOR WOOD. SEE SECTION 709.6 FOR WOOD
 ASSEMBLIES AND PROVIDE COMPLETE
 ASSEMBLY DETAIL TAKING INTO CONSIDERA-
 TION INTERIOR AND EXTERIOR EXPOSURE TO
 THE FIRE AS REQUIRED BY TABLE 600 FBC.
 2-ARCHITECT TO REVISE THE DIAPHRAGM
 SCHEDULE TO MATCH ENGINEERING SPECS.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. SPECIFY ANCHOR SIZE TO BE USED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.