Plan Review Notes For Permit 02101987 |
Permit Number |
02101987 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-26 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR. | | WALL ASSEMBLY AT ZERO LOT LINE. | | TABLE REFERENCED ON DETAIL 11/S3 IS | | FOR CONCRETE WALL ASSEMBLIES, NO WOOD. | | SEE SECTION 709.6 FOR WOOD ASSEMBLIES | | AND NEED COMPLETE ASSEMBLY TAKING INTO | | CONSIDERATION INTERIOR AND EXTERIOR | | EXPOSURE TO FIRE AS REQUIRED BY TABLE | | 600 FBC 2001. | | 2-REVISE SURVEY TO MATCH FLOOR PLANS. | | 3-ARCHITECT TO REVISE THE DIAPHRAGM | | SCHEDULE TO MATCH ENGINEERING SPECS. | | 4-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 5-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. NEED ANCHOR SIZE TO BE USED. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|