2002-11-09 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| 1) GENERAL NOTES, #1 & #5, CODE IS FBC- |
| 2001 NOT SBCCI OR COUNTY SWIMMING POOL |
| CODE. PLEASE CHANGE REFERENCES. |
| 2) CLEANING LINE NOT SHOWN ON PIPING |
| SCHEMATIC. |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) COMPLY WITH FBC-2001 SEC 424.2 |
| PRIVATE SWIMMING POOLS. (ADD TO NOTES) |
| 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-4 92. AND NSPI-5 (ADD TO NOTES |
| 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. (DETAIL) |
| 5) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) |
| 6) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| MENT AVOIDANCE. (DETAIL) |
| 7) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. |
| 9) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| BASE IN A MANNER THAT WILL ELIMINATE |
| STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| AL 4" THICK. (DETAIL) |
| 10) FBC-2001 424.2.8.1 VALVES SHALL BE |
| MADE OF MATERIALS THAT ARE APPROVED IN |
| THE FLA BLDG CODE, PLUMBING. THEY WILL |
| BE READILY ACCESSIBLE FOR MAINT. AND RE- |
| MOVAL. SEC 424.2.8.2 FULL WAY VALVES |
| SHALL BE INSTALLED TO INSURE PROPER FUN- |
| CTION OF THE FILTRATION AND PIPING SYS- |
| TEM. SEC 424.2.8.3 WHERE CHECK VALVES |
| ARE INSTALLED THEY SHALL BE OF THE SWING |
| OR VERTICAL CHECK PATTERNS. SEC 424.2.8. |
| 4 COMBINATION VALVES SHALL REQUIRE APP- |
| ROVAL OF THE ADMINISTRATIVE AUTHORITY |
| PRIOR TO THEIR INSTALLATION. |
| 11) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 12) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 13) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| |
| |
| |
| |
| |
| REVIEW BY KEN STEVENS |