Plan Review Notes For Permit 02101947 |
Permit Number |
02101947 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-04-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) PLANS SHALL BE SIGNED AND SEALED BY | | ARCHITECT OF RECORD. 61G1-16.002 - A | | TITLE BLOCK WITH FIRM NAME AND ADDRESS, | | FIRM LICENSE NUMBER, NAME OR IDENTIFIC- | | ATION OF PROJECT, DATE PREPARED, AND | | PRINTED NAME OF PERSON SEALING THE DOC- | | UMENT. 61G-16.004 | | 2) PLEASE PROVIDE CALCULATIONS FOR | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | 1/2 AREA OF ALL VERTICAL WALLS, AND ALL | | AREAS FROM ROOFS THAT DRAIN ON TO ROOF | | FROM ABOVE. - SHOW LOCATION OF ALL | | SECONDARY ROOF DRAINS/SCUPPERS AND SIZE | | OF EACH. | | 3) SHT A-2 PLUMBING NOTES #1, STATES | | "SEE SHEET 8 FOR ROOF DRAIN INSTALLATION | | DETAIL. NO DETAIL ON SHEET #8. PLEASE | | CLAIRFY. | | 4) PLEASE PROVIDE A STORM RISER DIAGRAM | | REQD. PER 104.3.1.1, FLA BLDG CODE | | ADMINISTRATIVE CODE, CHAPTER 1 & AMENDS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|