2003-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLANS SHALL BE SIGNED AND SEALED BY
 ARCHITECT OF RECORD. 61G1-16.002 - A
 TITLE BLOCK WITH FIRM NAME AND ADDRESS,
 FIRM LICENSE NUMBER, NAME OR IDENTIFIC-
 ATION OF PROJECT, DATE PREPARED, AND
 PRINTED NAME OF PERSON SEALING THE DOC-
 UMENT. 61G-16.004
 2) PLEASE PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 1/2 AREA OF ALL VERTICAL WALLS, AND ALL
 AREAS FROM ROOFS THAT DRAIN ON TO ROOF
 FROM ABOVE. - SHOW LOCATION OF ALL
 SECONDARY ROOF DRAINS/SCUPPERS AND SIZE
 OF EACH.
 3) SHT A-2 PLUMBING NOTES #1, STATES
 "SEE SHEET 8 FOR ROOF DRAIN INSTALLATION
 DETAIL. NO DETAIL ON SHEET #8. PLEASE
 CLAIRFY.
 4) PLEASE PROVIDE A STORM RISER DIAGRAM
 REQD. PER 104.3.1.1, FLA BLDG CODE
 ADMINISTRATIVE CODE, CHAPTER 1 & AMENDS.
  
 REVIEW BY KEN STEVENS