Plan Review Notes
Plan Review Notes For Permit 02101904
Permit Number 02101904
Review Stop E
Sequence Number 2
Notes
Date Text
2003-02-07 00:00:00************** UNSAT ************
  
 PLANS ARE BEING SUBMITTED COMPLETED AND
 HAVE THE FOLLOWING COMMENTS.
  
 1)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE. ONE SHOWS 100A PANEL AND OTHER
 SHOWS 200A?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW DISC AND PANEL. 110-9/215-5
  
 3)NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GROUNDING SYSTEM AT BLDG. 250-50
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 SOME CONN LOADS SHOWN ON PANEL SCHEDULE
 EXCEED 100A RATING OF PANEL, SOME ARE
 SHOWN UNDER?? PLEASE SUBMIT A LOAD
 CALC PER 220-3,10,11,13 ETC, ANY CONTIN-
 UOUS LOADS AT 125%. 215-3,230-42 ETC
 PLEASE ADJUST SERVICE AS NEEDED BY LOAD.
  
 5)NOTE: PLEASE SEE MECH PLAN, AHU HEAT
 IS SHOWN AT 5KW, ELECTRICAL PANEL/LOADS
 DO NOT CORRELATE, ELEC SHOWS AHU AT 13A
 AND #12 AWG ON 2P-20??? PLEASE ALSO SEE
 COMP UNIT SHOWN AS 2-P35A ON #12??
 PLEASE SEE 424-3 FOR OCP OF HEAT. MIN
 125% OF LOAD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372