Plan Review Notes
Plan Review Notes For Permit 02101904
Permit Number 02101904
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT P-1 WASTE AND VENT RISER DOES NOT
 REFLECT FLOOR PLAN. DRINKING FOUNTAIN
 NOT SHOWN ON RISER.
 2) SHT P-1 WASTE & VENT RISER, VENT REQ-
 UIRED FOR SHOWER & FLOOR SINK, AND VENT
 REQUIRED FOR SINK IN PRO SHOP.
 3) SHT P-1 INDIRECT WASTE SHALL DRAIN
 TO A FLOOR SINK. 802.3 - FLOOR DRAIN IS
 NOT AN APPROVED WASTE RECEPTOR.
 4) SHT P-1 WATER RISER DOES NOT REFLECT
 FLOOR PLAN. DRINKING FOUNTAIN NOT SHOWN
 ON WATER RISER DIAGRAM.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV.
 6) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER 607.3.2.
 PLEASE SHOW ON DETAIL
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377