2002-12-24 00:00:00DENIED:
  
 1.PLEASE PROVIDE ENERGY & COOLING LOAD
 CALCULATION AS PER 2001 FBC CHAPTER
 13 SECTION 400.0 & 407.1.ABCD.1.
  
 2.PLAN SHEET M1 GENERAL HVAC NOTES #2,
 INDICATES CONDENSING UNIT SHALL BE
 A 1.5 TON UNIT.EQUIPMENT SCHEDULE
 INDICATES A 3 TON. PLEASE CORRELATE.
  
 3.PLEASE CLARIFY R/A LOUVERD DOOR INTO
 THE STORAGE ROOM. AS PER 2001 FBC(M)
 602.1 RETURN AIR PLENUMS SHALL BE
 LIMITED TO UNINHABITED SPACES, THE
 STORAGE ROOM IS NOT CONSIDERED AN
 UNINHABITED SPACE.
  
 4.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" AWAY FROM THE BUILDING
 STRUCTURE, 2001 FBC 1503.4.4.
  
 5.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 6.EXHAUST FAN SCHEDULE INDICATES FANS
 ARE IN THE CLASS RMS? PLAN INDICATES
 EXHAUST FANS ARE IN THE RESTROOMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.