Plan Review Notes
Plan Review Notes For Permit 02101904
Permit Number 02101904
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00SHEET SP1 RE: THE HANDICAP PARKING
 SPACES.PLEASE PROVIDE SPECIFIC DESIGN
 INFORMATION, DO NOT QUOTE THE CODE
 SECTION.ALSO, THE SITE PLAN DOES NOT
 HAVE ANY DIMENSIONS LOCATING THE
 PROPOSED CONSTRUCTION ON THE PROPERTY.
  
 THE PLANS DO NOT INDICATE THE ROOF SLOPE
 OR THE WIND PRESSURE ZONES.
  
 PLEASE DEMONSTRATE HOW THE GABLE ENDS OF
 THE ROOF WILL MEET THE "STRUCTURALLY
 CONTINUOUS" REQUIREMENT OF FBC 2313.4.1.
  
 PLEASE PROVIDE A SPECIFIC METHOD OF
 INSTALLATION FOR THE "FIBER CEMENT
 PANELS" AS DEFINED BY THEIR NER 405
 LISTING.
  
 INDICATE THE ATTIC ACCESS REQUIRED BY
 FBC 2309.6.
  
 SHOW A STRUCTURAL DETAIL FOR THE
 TRANSITION/TERMINATION OF THE 8X16 TIE
 BEAM AT ELEVATION 109'-4" INTO THE CMU
 PRACTICE WALL.
  
 THE SPECIFICATIONS DECLARE AN F'M OF
 2000 PSI FOR THE MASONRY AND THE
 STRUCTURAL SHEET CALLS OUT 1500 PSI.
 PLEASE CLARIFY THE INTENT.THE
 SPECIFICATIONS ARE NOT SEALED BY THE
 ENGINEER.
  
 IF THE TEST REPORTS AND OR THE NOTICE OF
 ACCEPTANCE INFORMATION FOR THE DOORS
 WINDOWS AND ROOF COVERING ARE NOT
 INCLUDED WITH THE PERMIT APPLICATION, A
 SEPARATE PERMIT, FEES AND PLANS WILL BE
 REQUIRED.
  
 SHOW HOW THE GLAZED AREAS OF THE
 BUILDING EXTERIOR WILL RESIST HURRICANE
 MISSILE IMPACT.SEE FBC 1606.1.4.
2002-11-05 00:00:00TO ZONING BOX./WRT.