2002-12-03 00:00:00 | SHEET SP1 RE: THE HANDICAP PARKING |
| SPACES.PLEASE PROVIDE SPECIFIC DESIGN |
| INFORMATION, DO NOT QUOTE THE CODE |
| SECTION.ALSO, THE SITE PLAN DOES NOT |
| HAVE ANY DIMENSIONS LOCATING THE |
| PROPOSED CONSTRUCTION ON THE PROPERTY. |
| |
| THE PLANS DO NOT INDICATE THE ROOF SLOPE |
| OR THE WIND PRESSURE ZONES. |
| |
| PLEASE DEMONSTRATE HOW THE GABLE ENDS OF |
| THE ROOF WILL MEET THE "STRUCTURALLY |
| CONTINUOUS" REQUIREMENT OF FBC 2313.4.1. |
| |
| PLEASE PROVIDE A SPECIFIC METHOD OF |
| INSTALLATION FOR THE "FIBER CEMENT |
| PANELS" AS DEFINED BY THEIR NER 405 |
| LISTING. |
| |
| INDICATE THE ATTIC ACCESS REQUIRED BY |
| FBC 2309.6. |
| |
| SHOW A STRUCTURAL DETAIL FOR THE |
| TRANSITION/TERMINATION OF THE 8X16 TIE |
| BEAM AT ELEVATION 109'-4" INTO THE CMU |
| PRACTICE WALL. |
| |
| THE SPECIFICATIONS DECLARE AN F'M OF |
| 2000 PSI FOR THE MASONRY AND THE |
| STRUCTURAL SHEET CALLS OUT 1500 PSI. |
| PLEASE CLARIFY THE INTENT.THE |
| SPECIFICATIONS ARE NOT SEALED BY THE |
| ENGINEER. |
| |
| IF THE TEST REPORTS AND OR THE NOTICE OF |
| ACCEPTANCE INFORMATION FOR THE DOORS |
| WINDOWS AND ROOF COVERING ARE NOT |
| INCLUDED WITH THE PERMIT APPLICATION, A |
| SEPARATE PERMIT, FEES AND PLANS WILL BE |
| REQUIRED. |
| |
| SHOW HOW THE GLAZED AREAS OF THE |
| BUILDING EXTERIOR WILL RESIST HURRICANE |
| MISSILE IMPACT.SEE FBC 1606.1.4. |
2002-11-05 00:00:00 | TO ZONING BOX./WRT. |