Plan Review Notes For Permit 02101822 |
Permit Number |
02101822 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-07 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 1) FBC-2001424.2.7.1 POOL CIRCULATING | | PUMPS SHALL BE EQUIPPED ON THE INLET | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | STRAINER WHEN USED WITH A PRESSURE FIL- | | TER. (NOTES) | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 2) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | LED WITH FLANGES OR UNION CONNECTIONS | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|