Plan Review Notes For Permit 02101739 |
Permit Number |
02101739 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-08-19 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLORIDA STATUTES | | | | 1) 61G15023.002(2) SEE ATTACHED SHEET. | | ENGINEERS SHALL HAVE THEIR LICENSE NUM- | | BER ON EACH SHEET. (IN TITLE BLOCK) | | 2) ONLY THE FIXTURES WITHIN THE BATH- | | ROOM GROUPS SHALL CONNECT TO THE WET- | | VENTED HORIZONTAL BRANCH DRAIN. ANY | | ADDITIONAL FIXTURES SHALL DISCHARGE | | DOWNSTREAM OF THE WET VENT. SEC 909.1 | | SEE ATTACHED SHEET FOR RISER DIAGRAM | | THAT MEETS CODE REQUIREMENTS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|