Plan Review Notes
Plan Review Notes For Permit 02101739
Permit Number 02101739
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2003-08-27 00:00:001) SEPARATE PLANS AND PERMITS
 REQUIRED FIRE ALARM SYSTEM REMODEL.
  
 2) SEPARATE PLANS AND PEMRITS REQUIRE
 FOR FIRE SPRINKLER REMODEL.
  
 3) ALL NEW SMOKE DETECTORS THAT ARE
 INSTALLED SHALL BE POWERED BY THE
 HOUSE ELECTRICAL SERVICE. THESE SMOKE
 DETECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S
 REQUIREMENTS.
  
 4) ALL NEW STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES. ALL NEW
 STAIRS SHALL BE AT LEAST 44" WIDE.
  
 5) DOORS # 5 AND # 6 ARE NOT NOTED
 ON THE DOOR SCHEDULE. ALSO NO
 INFORMATION PROVIDED WITH REGARDS
 TO SELF-COSING DEVICES INSTALLED
 ON THE SLEEPING ROOM DOORS.
  
 6) ARE ANY FIRE SPRINKLERS PLANNED TO
 PROTECT THE WOOD TRUSSES.
  
 7) NO INFORMATION PROVIDED FOR INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 8) IN SOME AREAS OF THE PLANS 5/8"
 DRYWALL IS NOTED. 5/8" TYPE X DRYWALL
 IS REQUIRED.
  
 9) DOESN'T THE KITCHEN DOOR BLOCK THE
 EGRESS HALLWAY BY MORE THEN 50 %.
  
 10) PLEASE INDICATE THE EVACUATION
 CAPABILITY OF THE NEW PROPOSED
 RESIDENTS. WILL THEY BE SLOW, PROMPT
 OR IMPRACTICAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910