2003-08-27 00:00:00 | 1) SEPARATE PLANS AND PERMITS |
| REQUIRED FIRE ALARM SYSTEM REMODEL. |
| |
| 2) SEPARATE PLANS AND PEMRITS REQUIRE |
| FOR FIRE SPRINKLER REMODEL. |
| |
| 3) ALL NEW SMOKE DETECTORS THAT ARE |
| INSTALLED SHALL BE POWERED BY THE |
| HOUSE ELECTRICAL SERVICE. THESE SMOKE |
| DETECTORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER'S |
| REQUIREMENTS. |
| |
| 4) ALL NEW STAIRS AND RAMPS SHALL HAVE |
| HANDRAILS ON BOTH SIDES. ALL NEW |
| STAIRS SHALL BE AT LEAST 44" WIDE. |
| |
| 5) DOORS # 5 AND # 6 ARE NOT NOTED |
| ON THE DOOR SCHEDULE. ALSO NO |
| INFORMATION PROVIDED WITH REGARDS |
| TO SELF-COSING DEVICES INSTALLED |
| ON THE SLEEPING ROOM DOORS. |
| |
| 6) ARE ANY FIRE SPRINKLERS PLANNED TO |
| PROTECT THE WOOD TRUSSES. |
| |
| 7) NO INFORMATION PROVIDED FOR INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS. |
| |
| 8) IN SOME AREAS OF THE PLANS 5/8" |
| DRYWALL IS NOTED. 5/8" TYPE X DRYWALL |
| IS REQUIRED. |
| |
| 9) DOESN'T THE KITCHEN DOOR BLOCK THE |
| EGRESS HALLWAY BY MORE THEN 50 %. |
| |
| 10) PLEASE INDICATE THE EVACUATION |
| CAPABILITY OF THE NEW PROPOSED |
| RESIDENTS. WILL THEY BE SLOW, PROMPT |
| OR IMPRACTICAL. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |