Plan Review Notes For Permit 02101739 |
Permit Number |
02101739 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-08-19 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SEE NOTES FROM LAST | | REVIEW PERTAINING TO PANEL SCHEDULE AND | | CORRELATION OF LOADS/AWG'S AND OCP. | | PLEASE SEE GEN LT ETC 20OCP ON #14, | | DRYER SHOWN AS 120V | | PLEASE SEE OVEN MICR AT 12KW W/ 40A OCP | | | | 2)NOTE: PLEASE SEE PREVIOUS NOTES | | THAT LIST BATHS TO BE DEDICATED AS | | 20A AND #12 AWG. 210-11C-3/ 210-52D | | | | 3)NOTE: PLEASE SEE MISSING INFORMATION | | REQ'D ON TITLE BLOCK FOR ENGINEER OF | | RECORD UNDER FAC/FS 61G15-23.002/ 471 | | | | PLEASE SEE LETTER ATTACHED ONCE AGAIN | | FOR FS 553.80(2)(B) WITH RESPECT TO | | DESIGN PROFESSIONAL. PLEASE NOTE, A | | 4X FEE FOR PLAN WILL BE ACCESSED FOR THE | | PLAN REVIEW PORTION IF COMMENTS ARE NOT | | ADDRESSED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | PLEASE SEE GROUNDING ELECTRODE CONDUCTOR | | IT WAS GIVEN IN NOTES AT LAST MEETING | | THIS NEEDS TO BE SIZED PER 250-66 | | THIS HAS NOT BEEN CHANGED TO DATE, STILL | | SHOWS #4 |
|