2003-08-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/2/03:
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE
 THE ENGINEERS LICENSE NUMBER SHALL BE
 PRINTED ON EACH SHEET.
  
 7) FBC 3401.7.1ADDITIONS TO EXISTING
 BUILDINGS.AS THE AREA OF THE ADDITION
 EXCEEDS 25% OF THE AREA OF THE EXISTING
 BUILDING, THE EXISTING BUILDING AND THE
 ADDITION SHALL BE MADE TO COMPLY WITH
 ALL, EXCEPT STRUCTURAL, REQUIREMENTS OF
 THE CODE FOR A BUILDING OF AREA EQUAL TO
 THE COMBINED AREA.THIS REQUIREMENT
 GIVES RISE TO COMMENTS 26 TO 31 BELOW.
  
 10) SHEET R1, TRUSS CONNECTORS/ANCHORS.
 THE STATED ANCHORS 'HCLH/HCRH', SHA-6'
 AND 'HD 2X' ARE ALL HUGHES REFERENCES.
 HUGHES ARE NO LONGER SUPPLIERS OF
 ANCHORS.SPECIFY ALTERNATIVE ANCHORS.
 ALSO, THE SPECIFIED UPLIFT AND FASTENERS
 FOR THE 'HETA20' TRUSS ANCHOR DO NOT
 CORRELATE TO THE UPLIFT AND FASTENERS IN
 THE 2003 SIMPSON CATALOGUE.AMEND SHEET
 R1.FINALLY, THE ROOF PLAN SHALL BE
 AMENDED TO SHOW WHAT TYPE OF ANCHOR IS
 TO BE USED IN EACH LOCATION.
  
 12) FBC 11-4.1.2(1)EXTERIOR RAMPS TO
 THE NEW HALL AND THE NEW PATIO HALL.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 AMEND THE PLANS TO SHOW THE SURFACE
 MATERIAL (PAVERS, CONCRETE, ASPHALT,
 GRASS, GRAVEL?) LEADING TO THE BASE OF
 THE RAMPS AND TO SHOW CLEAR, LEVEL
 ACCESS TO THE RAMPS FROM THE ACCESSIBLE
 PARKING AND SIDEWALK.
  
 14) PRODUCT APPROVAL DOCUMENTS:
 -DRAWING SHEET #2 OF THE STEEL STORM
 PANEL SHUTTER PRODUCT APPROVAL IS
 MISSING.ALSO, DRAWING SHEET #1 IS A
 POOR COPY AND IS NOT LEGIBLE.SUBMIT
 LEGIBLE COPPIES OF DRAWING SHEETS 1 & 2
 SEE NOTE** BELOW.
 -THE ALUMINUM SINGLE HUNG WINDOW
 PRODUCT APPROVAL NOA# 02-0612.04 IS FOR
 A SINGLE UNIT APPLICATION ONLY.SUBMIT
 A PRODUCT APPROVAL FOR AN APPROPRIATE
 STRUCTURAL MULLION FOR WINDOW TYPE B
 (KITCHEN WINDOW).SEE NOTE** BELOW.
 -THE 'GLADIATOR' O/S GLAZED STEEL
 DOOR PRODUCT APPROVAL NOA# 99-1007.01 IS
 MISSING SHEET 6 OF 7.SEE NOTE** BELOW.
 -THE MODIFIED BITUMEN ROOF SYSTEM
 PRODUCT APPROVAL NOA# 00-0331.08 SHALL
 BE MARKED TO SHOW WHICH SYSTEM TYPE IS
 TO BE USED.
 **COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
  
 26) FBC 13-103.1.1.1SUBMIT AN ENERGY
 CODE COMPLIANCE FORM FOR THE WHOLE
 BUILDING (SEE COMMENT 7 ABOVE).THE
 FORM MUST BE SIGNED BY THE PREPARER,
 BUILDING OWNER AND THE DESIGN
 PROFESSIONALS RESPONSIBLE FOR THE
 ARCHITECTURAL, MECHANICAL, PLUMBING,
 ELECTRICAL AND LIGHTING SYSTEMS.
  
 27) FBC 1007.3ANNOTATE THE PLANS TO
 SHOW THAT THE EXISTING STAIR TREADS ARE
 MIN. 11" AND RISERS ARE MAX. 7".
  
 28) FBC 1007.4THE STAIR SHALL HAVE A
 FULL LANDING BETWEEN THE TOP RISER AND
 THE DOOR.THE DOOR AND ASSOCIATED WALL
 SHALL BE REPOSITIONED.AMEND THE PLANS
 TO SHOW THE PROPOSAL FOR COMPLIANCE.
  
 29) 1007.5THE EXISTING STAIR HANDRAIL
 SHALL BE MADE TO COMPLY WITH ALL OF THE
 REQUIREMENTS OF FBC 1007.5, INCLUDING:
 -HANDRAIL HEIGHT SHALL BE BETWEEN
 34" (36" TO ALSO COMPLY WITH FBC 1026.5)
 AND 38" ABOVE THE LEADING EDGE OF THE
 TREAD.
 -HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF THE STAIR.
 -HANDRAIL CROSS-SECTIONAL SHAPE AND
 SIZE SHALL COMPLY.
 -THE HANDRAILS SHALL EXTEND AT LEAST
 12" HORIZONTALLY BEYOND THE TOP RISER OF
 THE FLIGHT AND SHALL CONTINUE TO SLOPE
 PAST THE BOTTOM RISER FOR A DISTANCE
 EQUAL TO ONE TREAD.
 -THE HANDRAIL/GUARDING AND
 ATTACHMENTS SHALL MEET THE STRENGTH
 REQUIREMENTS OF FBC 1608.2.1.1 TO
 FBC 1608.2.2.4
  
 30) FBC 1015.3THE EXISTING STAIR
 GUARDING SHALL REJECT THE PASSAGE OF A
 4" SPHERE.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 31) FBC 2405.2 THE GLAZING IN THE SHOWER
 ENCLOSURES AND WINDOWS IN BATH# 4 & 6
 (IF THE BOTTOM EDGE OF THE GLASS IS NOT
 GREATER THAN 60" ABOVE THE STANDING
 SURFACE) IS IN A HAZARDOUS LOCATION AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 32) FBC 1606.1.7THE PLANS DO NOT STATE
 THE DESIGN WIND PRESSURE ON THE ROOF FOR
 SELECTION OF AN APPROPRIATE ROOF SYSTEM.
 ANNOTATE THE PLANS.
  
 33) FBC 3502 THE NOTES ADDED TO SHEET A3
 SHALL BE AMENDED AS FOLLOWS:
 -MASONRY WALL NOTE D REFERS TO
 ASTM C 90-75 FOR CONCRETE BLOCKS.THE
 STANDARD REFERENCED IN THE CODE IS
 ASTM C 90-90
 -DESIGN DATA NOTE A REFERS TO
 ACI 318-77 FOR STRUCTURAL CONCRETE.THE
 STANDARD REFERENCED IN THE CODE IS
 ACI 318-99
 -DESIGN DATA NOTE F REFERS TO
 ASTM A 185-73 FOR WELDED WIRE FABRIC.
 THE STANDARD REFERENCED IN THE CODE IS
 ASTM A 185-92
 -PRE-ENGINEERED WOOD TRUSSES NOTE B
 REFERS TO PALM BEACH COUNTY. THIS SHOULD
 BE CITY OF WEST PALM BEACH.
 -WOOD FRAMING NOTE D REFERS TO
 STANDARD BUILDING CODE.THIS SHOULD BE
 FLORIDA BUILDING CODE
  
 34) 713.13(2) FL. STATUTES.THE
 DESCRIBED WORKS DID NOT COMMENCE WITHIN
 90 DAYS OF RECORDING THE NOTICE OF
 COMMENCEMENT SO THE NOTICE IS VOID AND
 OF NO FURTHER EFFECT.IT SHALL BE RE-
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.
  
 35)HISTORIC PRESERVATION DIVISION
 STAMPED THE PLANS AS 'APPROVED' ON
 10/28/02.THE PLANS HAVE BEEN THROUGH
 A NUMBER OF REVISIONS SINCE THEN.WHEN
 THE REVISED PLANS HAVE BEEN PASSED BY
 THE CONSTRUCTION SERVICES DEPARTMENT
 THEY SHOULD BE TAKEN, TOGETHER WITH THE
 STAMPED 'OLD' PLANS, FOR REVIEW AND
 RE-STAMPING BY HISTORIC PRESERVATION
 DIVISION.
  
 36) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]