2003-04-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FHA-98 AMEND. DESIGN MANUAL |
| |
| 1) FROM PREVIOUS REVIEWS. SHT A5 PLEASE |
| SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS FOR BOTH THE OLD |
| AND NEW ROOFS. (NEW PARAPET HEIGHT |
| EFFECTS BOTH ROOFS.) SHOW SQUARE FOOTAGE |
| FOR ALL ROOFS, INCLUDING 1/2 AREA OF ALL |
| VERTICAL WALLS AND ANY AREA OF ROOFS |
| THAT DRAIN ONTO THE ROOFS FROM ABOVE. |
| SEE SECTIONS 1106 & 1107. |
| 2) NOW THAT USAGE AND OCCUPANCY IS CLEAR |
| THE FAIR HOUSING ACT SHALL BE ENFORCED. |
| PLEASE SHOW COMPLIANCE WITH REQUIREMENTS |
| 1 THRU 7. SPECIFY "A" OR "B" TYPE BATH- |
| ROOMS. SHOW ALL BACKING PER REQUIREMENT |
| #6. SHOW ALL CLEAR FLOOR SPACE ON FLOOR |
| PLAN. SHOW ALL PROPER DIMENSIONS FOR |
| FIXTURES INCLUDING HEIGHT, CENTER OF |
| FIXTURE TO WALL ECT. |
| 4) WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |