Plan Review Notes
Plan Review Notes For Permit 02101739
Permit Number 02101739
Review Stop P
Sequence Number 3
Notes
Date Text
2003-04-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 AMEND. DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEWS. SHT A5 PLEASE
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR BOTH THE OLD
 AND NEW ROOFS. (NEW PARAPET HEIGHT
 EFFECTS BOTH ROOFS.) SHOW SQUARE FOOTAGE
 FOR ALL ROOFS, INCLUDING 1/2 AREA OF ALL
 VERTICAL WALLS AND ANY AREA OF ROOFS
 THAT DRAIN ONTO THE ROOFS FROM ABOVE.
 SEE SECTIONS 1106 & 1107.
 2) NOW THAT USAGE AND OCCUPANCY IS CLEAR
 THE FAIR HOUSING ACT SHALL BE ENFORCED.
 PLEASE SHOW COMPLIANCE WITH REQUIREMENTS
 1 THRU 7. SPECIFY "A" OR "B" TYPE BATH-
 ROOMS. SHOW ALL BACKING PER REQUIREMENT
 #6. SHOW ALL CLEAR FLOOR SPACE ON FLOOR
 PLAN. SHOW ALL PROPER DIMENSIONS FOR
 FIXTURES INCLUDING HEIGHT, CENTER OF
 FIXTURE TO WALL ECT.
 4) WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692