Plan Review Notes For Permit 02101739 |
Permit Number |
02101739 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-04-11 00:00:00 | *********** UNSAT *************** | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, | | SHOWS #1`S AND #3 FOR 200A DISC AND | | PANEL? PLEASE SIZE PER 310-16 | | | | 2)NOTE: PLEASE SEE CIRCUITS ON PANEL | | SCHEDULE/LOAD CALCS. SMALL APPL AND | | GEN LT SHOWN AT 240V? PLEASE ALSO SEE | | CIRCUITS #`S SHOWN FOR SM APPL ,, SHOWS | | TWO CIRCUITS AND SHOWS LOAD FOR THREE | | CIRCUITS?PLEASE CLARIFY | | | | 3)NOTE: PLEASE SEE PLANS,ALMOST ALL | | RECEPTS AND LTS ARE SHOWN ON TWO CIRCUIT | | -S 21&28. PLEASE SEE 210-52D/210-11C3 | | BATHS MAY NOT BE ON WITH OTHER CIRCUITS, | | PLEASE ALSO CLARIFY, SOME CIRCUITS ARE | | SHOWN GOING OVER TO EXISTING BLDG CROSS- | | ING OVER TO AREA WITH SEPARATE SERVICE? | | 210-25 PLEASE ADJUST CIRCUITS. | | | | 4)NOTE: PLEASE SEE 250-122 FOR SIZING | | OF EQUIPMENT GROUNDING CONDUCTOR FROM | | NEW MAIN TO PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|