Notes
Date Text
2003-04-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM,
 SHOWS #1`S AND #3 FOR 200A DISC AND
 PANEL? PLEASE SIZE PER 310-16
  
 2)NOTE: PLEASE SEE CIRCUITS ON PANEL
 SCHEDULE/LOAD CALCS. SMALL APPL AND
 GEN LT SHOWN AT 240V? PLEASE ALSO SEE
 CIRCUITS #`S SHOWN FOR SM APPL ,, SHOWS
 TWO CIRCUITS AND SHOWS LOAD FOR THREE
 CIRCUITS?PLEASE CLARIFY
  
 3)NOTE: PLEASE SEE PLANS,ALMOST ALL
 RECEPTS AND LTS ARE SHOWN ON TWO CIRCUIT
 -S 21&28. PLEASE SEE 210-52D/210-11C3
 BATHS MAY NOT BE ON WITH OTHER CIRCUITS,
 PLEASE ALSO CLARIFY, SOME CIRCUITS ARE
 SHOWN GOING OVER TO EXISTING BLDG CROSS-
 ING OVER TO AREA WITH SEPARATE SERVICE?
 210-25 PLEASE ADJUST CIRCUITS.
  
 4)NOTE: PLEASE SEE 250-122 FOR SIZING
 OF EQUIPMENT GROUNDING CONDUCTOR FROM
 NEW MAIN TO PANEL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  